The G2 Series provides a positive ground indication through the use of an intrinsically safe monitoring circuit driving a switching relay. Upon connection of the self-releasing clamp and cable to a conducting material, the intrinsically safe circuit is completed and the operator will be shown a green light to indicate that a ground connection has been established.  

While most competing systems only monitor the path from the ground unit to the clamp, the G2 series also employs a segregated cable connection to actual ground, which is also monitored for low resistance.  An interruption in either path (indicated by any resistance above 5 ohms) will shut down the system. 

The system can also be interlocked with filling equipment to ensure that no flammable product can be transferred until the ground is established.  If the circuit is broken by release of the grounding clamp or other ground interruption, the control relay will open and a red light will be displayed.  Any filling equipment that is controlled by the system will also be halted until the ground is re-established.

The G2 Series systems will do the following: shut down a pump or valve; sound an alarm; show a red light when conditions are unsafe; show a green light when conditions are safe; open contacts on a computer; indicate that static path to ground has integrity and receive permissive signals from a computer control.

Standard options include a choice of aluminum or bronze clamp, straight or self-coiling cable, and a variety of cable storage and retracting reels.

  • 5 Ohm set resistance point

  • Unit measures 13" H x 11" W x 5" D

  • 110V power required, ¾" NPT connection. (220V available)

  • Moisture drain

  • Approvals: cULus Class 1, Division 1, Group D. Class 2, Division 1, Group E, F, G.

Part No. Clamp Cable
G2-25IG-A2 Aluminum GATP-IP2 25' straight SOOW
G2-25IG-A2CC Aluminum GATP-IP2 25' coiled SEOOW
G2-25IG-B1 Bronze G40-PMIP1 25' straight SOOW
G2-25IG-B1CC Bronze G40-PMIP1 25' coiled SEOOW

The G2 Series Electronic Ground Indicating Systems can be used as a Deadman System with a deadman switch in place of the ground clamp.  When the operator depresses the switch, the intrinsically safe monitoring circuit drives a switching relay that can, for instance, switch on a pump and initiate product flow.  If the operator releases the switch at any time, the relay opens and product flow is immediately stopped. 

Approvals:  cULus Class 1, Division 1, Group D.  Class 2, Division 1, Group E, F, G.

Options include red and green indicating lights, coiled cables, and a variety of cable storage and retracting reels.

Part No. Red/Green Light Indicators Cable
G2-25IG-DM Yes 25' straight SOOW
G2-50IG-DM Yes 50' straight SOOW
G2-25IG-DMNL No 25' straight SOOW
G2-50IG-DMNL No 50' straight SOOW
LE95100163DM (NSN 4930-20-008-7994) Deadman switch 100' 16/3 SOW cord on heavy-duty reel